Liquid-Retaining Structure Design (Detention / Sediment Basin, Tank, U-Channel)

Overall flotation of buried detention / sediment basins, reservoirs and U-shaped open channels (with quantified options when insufficient), two-face reinforcement of walls and base slab, and crack control for liquid tightness (code bar spacing, crack width or steel stress limit).

Design basis for this page ▾
Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350)

Design basis as reported by the calculation core: Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350)
Design follows the Taiwan codes named in the basis line; the direct crack-width option uses the EN 1992 clauses named there. This is a Taiwan-code calculation offered for reference: bar sizes are D13–D32 and strengths are entered in kgf/cm².

Recalculates in your browser as you edit inputs; Free sample Word report and DXF for this calculator; With a license: formal Word and DXF export, plus online project reports from the Project List.

Interactive Engineering Workstation (SI Units, Reference Calculation)
SI units (reference calculation)
Free Samples and Pricing
A public sample produced by the production service from this page's standard example and sealed with a verification code: open it in Word or AutoCAD and check it on the Verify page. Not for PE sealing or submittal.
Single-export pass: US$19 for one calculator, 3 formal exports in total within 24 hours of the first; full credit toward an upgrade within 30 days, full refund before the first export
Single-export passes (one calculator, 3 exports within 24 hours), 30-day passes, annual plans and perpetual licenses; printable quotes for purchase orders.
Formal export and the Project List are on the workbench toolbar above:
Licensed users can formally export this calculator's Word report (with a verification code and server time witness) and AutoCAD DXF drawing, or add several calculators to the free Project List and export a multi-chapter project report online, with nothing to install on a Mac. Projects with DEM terrain or GIS files can run in the heavy cloud computation or in the HydroStudio desktop edition.
The summary lists the basis, key results and check verdicts; its first line marks it as an online preview, not for PE sealing or submittal.
Download the Offline Workbench (Single HTML File, 39 Tools)
No install and no email required. It contains the same calculation core as this site; results are also a preview, not for sealed submittals.

Check Summary Preview (Software Format; Auto-Populated)

Liquid-Retaining Structure Design (Detention / Sediment Basin, Tank, U-Channel): check summary (software format)
Calculation basis: Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350)
Check item Trial value Status
Wall Outer face: φMn ≥ Mu and minimum steel63.68 kN·m/m ≥ 62.50OK
Wall Outer face: crack control17.5 cm ≤ 31.5OK
Wall Inner face: φMn ≥ Mu and minimum steel49.82 kN·m/m ≥ 35.75OK
Wall Inner face: crack control22.5 cm ≤ 40.3OK
Wall: φVc ≥ Vu158.93 kN/m ≥ 54.71OK
Bottom slab Outer face: φMn ≥ Mu and minimum steel81.78 kN·m/m ≥ 71.06OK

Summary of the online calculation (software format) for checking by the designer and an independent checker. Final submittals require review and seal by the licensed Professional Engineer in responsible charge.

Desktop edition: calculation reports and cross-module quantity reconciliation

1. Calculation reports: with a license, the desktop edition writes Word (.docx) and Excel (.xlsx) calculation reports and DXF drawings without the trial watermark, listing the inputs, the equations used and the results; in trial mode the step-by-step detail is hidden. For this calculator alone, licensed users can also sign in on the calculator above and formally export a single-tool Word report (with a verification code) and DXF drawing. The Pro plan (all modules) is US$990 per year; see Pricing for monthly, perpetual and team plans.
2. Cross-module reconciliation: desktop project runs carry the design peak flow into downstream channel, culvert and bridge hydraulics; terrain cut/fill into the earthwork balance, cost and carbon tables; structural concrete, formwork and rebar take-off into the cost and carbon tables; slope and excavation safety-factor thresholds into construction monitoring trigger levels.
3. Agency plan reviewers and university faculty can request a complimentary review or teaching license (link below).

Desktop pricing (Pro US$990/yr) Download the desktop trial Complimentary license for agency reviewers and faculty
Scope and responsibility: This page is a single-calculator trial run; cross-module quantity reconciliation is done in desktop project runs. Problems outside this calculator's scope (see the FAQ) need an appropriate analysis method. Final submittals require review and seal by a licensed Professional Engineer. Preliminary reinforced concrete design and flotation check to the Taiwan code named in the basis line; ACI 350 environmental durability factors are not applied.

Standard example (calculation core defaults)

The worked example below was computed by the calculation core when this page was built; entering the same inputs above reproduces it. Verification cases, tolerances and actual differences for the calculation core are listed on the Benchmarks page.

The standard example uses the default inputs of the calculation core. Every number below was produced by the core when this page was built; nothing on this page is computed by hand.

Every number in this example was produced by the calculation core (WebAssembly) when this page was built. This calculator computes to the documents named in its basis line and works in SI units; use the unit button in the calculator to view US customary equivalents. Basis reported by the core: Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350)

1. Input Parameters

Design ParameterValueUnit
Structure TypeOpen top (U-channel, open sediment basin; cantilever walls)—
Clear Width4m
Clear Height2.5m
Wall Thickness0.3m
Base Slab Thickness0.35m
Base Slab Projection0m
External Backfill Height(blank)m
Backfill Unit Weight18kN/m³
Backfill Saturated Unit Weight20kN/m³
Lateral Earth Pressure Coefficient(blank)—
Surface Surcharge10kPa
External Groundwater Level(blank)m
Internal Water Depth(blank)m
Required Flotation Safety Factor(blank)—
Allowable Uplift Resistance of Anchors / Tension Piles(blank)kN/m
Concrete Strength f'c280kgf/cm²
Rebar Yield Strength fy4200kgf/cm²
Minimum Tension Steel Ratio(blank)—
Bar SizeSelected by program—
Crack Control MethodTaiwan concrete code Art. 24.3.2 maximum bar spacing—
Basin Length(blank)m

2. Computed Results (calculation core output)

OutputResult
Max flexural utilization Mu / φMn0.982
Max shear utilization Vu / φVc0.344
Max crack control utilization (value / limit)0.626
Rebar weight (estimate)152.9 kg/m
Concrete3.110 m³/m

Verification Checks (calculation core output)

Verification ItemComputed ResultGoverning Limit / CriterionStatusBasis
Wall Outer face: φMn ≥ Mu and minimum steel63.68 kN·m/m≥ 62.50PASSTaiwan Design Code for Concrete Structures (2023)
Wall Outer face: crack control17.5 cm≤ 31.5PASS—
Wall Inner face: φMn ≥ Mu and minimum steel49.82 kN·m/m≥ 35.75PASSTaiwan Design Code for Concrete Structures (2023)
Wall Inner face: crack control22.5 cm≤ 40.3PASS—
Wall: φVc ≥ Vu158.93 kN/m≥ 54.71PASSTaiwan Design Code for Concrete Structures (2023)
Bottom slab Outer face: φMn ≥ Mu and minimum steel81.78 kN·m/m≥ 71.06PASSTaiwan Design Code for Concrete Structures (2023)
Bottom slab Outer face: crack control15.0 cm≤ 31.6PASS—
Bottom slab Inner face: φMn ≥ Mu and minimum steel60.57 kN·m/m≥ 57.68PASSTaiwan Design Code for Concrete Structures (2023)
Bottom slab Inner face: crack control20.0 cm≤ 31.9◇ Not judged
Not judged: This section is in axial tension under the governing service load combination: the service steel stress fs is calculated on the cracked section in flexure without the axial force, so fs may be underestimated (the bar spacing limit or steel stress limit checked against it is unconservative); until a tension-and-flexure section model and an independent worked example are in place, this program makes no crack control judgement; the calculated values are listed for reference.
—
Bottom slab: φVc ≥ Vu91.60 kN/m≥ 15.95PASSTaiwan Design Code for Concrete Structures (2023)

3. Calculation Steps (calculation core output, SI units)

[HyGeoWorks online preview - not for PE sealing or submittal]
Outer width 4.60 m (full base width 4.60 m), outer height 2.85 m; concrete 3.110 m³/m; internal water depth 2.50 m; external backfill height 2.85 m
Load combinations: U1 = 1.4(D + F), U2 = 1.2D + 1.6H + 1.6L, U3 = 1.2(D + F) + 0.9H; service S1 = D + F, S2 = D + H + L, S3 = D + F + H
Reinforcement and crack control (per metre of length) (4 rows)
MemberTension faceMu (kN·m)Ms (kN·m)Required As (cm²)Bars @ spacing (cm)φMn (kN·m)fs (kgf/cm²)Crack control: value / limitVerdict
WallOuter face62.5039.067.10D13@17.563.68241717.5/31.5 cmPASS
WallInner face35.7525.545.40D13@22.549.82201622.5/40.3 cmPASS
Bottom slabOuter face71.0643.847.31D13@15.081.78211215.0/31.6 cmPASS
Bottom slabInner face57.6841.206.30D13@20.060.57239420.0/31.9 cmNot judged
Shear (2 rows)
MemberThickness (cm)Vu (kN)φVc (kN)Vc basisGoverning combination
Wall3054.71158.930.53λ√fc'·bw·dU2 = 1.2D + 1.6H + 1.6L (empty, external earth and water pressure)
Bottom slab3515.9591.60Table 22.5.5.1(c) with size effect λs (Art. 22.5.5.1.3)U2 = 1.2D + 1.6H + 1.6L (empty, external earth and water pressure)

Assumptions and Limits Stated by the Calculation Core

Frequently Asked Questions

Common questions about this calculator and its basis are answered below. Final submittals require review and seal by a licensed Professional Engineer.

Which design basis does this calculator apply?

Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350). Design follows the Taiwan codes named in the basis line; the direct crack-width option uses the EN 1992 clauses named there. This is a Taiwan-code calculation offered for reference: bar sizes are D13–D32 and strengths are entered in kgf/cm².

What assumptions and limits does the calculation core state for this tool?

Load classification (Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7): the contained liquid is fluid load F, with the same load factors and combinations as dead load; external earth pressure and pore-water pressure are H (1.6; 0.9 where permanent and counteracting the primary load). Lateral earth pressure coefficient K = 0.5 (0.5 when not given: the Taiwan Building Foundation Design Code (2023) Art. 7.3.1 requires an at-rest coefficient of not less than 0.5, to be raised for overconsolidated soil); backfill surface height 2.85 m, groundwater height 0.00 m (above underside of base slab). Analysis model: plane frame on member centrelines with uniform base reaction; section strength design includes axial tension (flexure and shear) and neglects axial compression (conservative). Not covered: two-way slab action along the tank length and partition walls, restrained thermal and shrinkage effects, seismic hydrodynamic pressure, design of construction joints and waterstops. Sections in axial tension (Taiwan Design Code for Concrete Structures (2023) Arts. 22.2 and 22.4, tension-controlled φ = 0.90): where the moment about the tension steel Ms = Mu − Nu(d − h/2) > 0, As = As(Ms) + Nu/(φfy); where Ms ≤ 0 (whole section in tension, concrete neglected), moments are taken about the other layer, As = [Nu(h/2 − d') + Mu]/[φfy(d − d')], with d' estimated as the other face cover plus half the same bar diameter. Shear Vc includes Nu/(6Ag) (Table 22.5.5.1; tension negative, Vc not less than 0). Crack control: maximum bar spacing of Art. 24.3.2 (using the calculated service-load steel stress). This is a general building provision and does not address liquid tightness; where tightness matters, use the crack width or steel stress limit method. This section is in axial tension under the governing service load combination: the service steel stress fs is calculated on the cracked section in flexure without the axial force, so fs may be underestimated (the bar spacing limit or steel stress limit checked against it is unconservative); until a tension-and-flexure section model and an independent worked example are in place, this program makes no crack control judgement; the calculated values are listed for reference. Strength design follows the Taiwan MOI Design Code for Concrete Structures of Buildings (2023 edition); USACE EM 1110-2-2104 and ACI 350 criteria are not implemented.

Where is the calculation performed, and can the result be sealed or submitted?

The calculation runs in your browser, in the same WebAssembly calculation core this page loads. The result is an online preview: its first line reads "[HyGeoWorks online preview - not for PE sealing or submittal]".

Can I recalculate without a network connection?

Yes. "Download the offline workbench" on this page saves one HTML file that contains the workbench and the same calculation core; opened from disk it recalculates without a network connection.

USD Pricing · Checkout by Stripe · Printable USD Quotation

From the Online Preview to the HydroStudio Desktop Edition: Reports Without the Trial Watermark

The free online preview is not for PE sealing or submittal and has no Word report, DXF drawing or verification code. Licensed users can sign in on the calculator and formally export a single-tool Word report (with a verification code) and DXF drawing. Several calculators can be combined in the Project List and exported online as a multi-chapter project report, and projects with terrain or GIS files can run in the heavy cloud computation. For interactive 2D models and large simulations, the HydroStudio desktop edition (Windows 10/11, 64-bit) opens the exported .toml project and, with a license, writes report.docx, a report.xlsx with live formulas and DXF drawings without the trial watermark. Sealing and submittal remain the responsibility of the licensed engineer.

Monthly
Pro monthly
$119 / month
One discipline: $69 / month. Renews monthly until canceled; cancel any time before the next renewal and keep using it to the end of the paid month.
Buy monthly ($119/mo)
30 days
30-day pass
$79 / 30 days, one discipline
All modules: $135. One payment; it does not renew. The pass fee can be credited once toward an annual or perpetual license of the same discipline or a higher plan bought within 30 days after the pass ends, with the same email and in the same currency.
Buy a 30-day pass (from $79)
Quotation
Printable USD quotation
For any plan, including Firm (from 3 seats) and Enterprise (from 10 seats), which are sold only to businesses and other organizations, not to individual buyers: print the quotation or save it as a PDF for your purchasing process.
Request a printable USD quotation

Compare all plans, including 90-day passes and perpetual licenses

Checkout is processed by Stripe; a tax ID can be entered at checkout, and for one-time payments Stripe issues an invoice showing the buyer's name and tax ID. Procurement follows your organization's own rules.

Explore All 31 Tools (20 US Customary + 11 Reference: Basis Stated on Each Page)

Need to edit terrain, 2D flood models and design alternatives interactively on your computer, or see 3D views drawn from your project data? Use the HydroStudio desktop edition:
Download the Desktop Trial
No credit card or phone number is needed to download. Without a license it runs as a trial: local calculation and 3D viewing work, exported reports and drawings carry a trial watermark (not for submittal), and some built-in data libraries are limited. Plans and prices are on the Pricing page.