Check Summary Preview (Software Format; Auto-Populated)
| Check item | Trial value | Status |
|---|---|---|
| Wall Outer face: φMn ≥ Mu and minimum steel | 63.68 kN·m/m ≥ 62.50 | OK |
| Wall Outer face: crack control | 17.5 cm ≤ 31.5 | OK |
| Wall Inner face: φMn ≥ Mu and minimum steel | 49.82 kN·m/m ≥ 35.75 | OK |
| Wall Inner face: crack control | 22.5 cm ≤ 40.3 | OK |
| Wall: φVc ≥ Vu | 158.93 kN/m ≥ 54.71 | OK |
| Bottom slab Outer face: φMn ≥ Mu and minimum steel | 81.78 kN·m/m ≥ 71.06 | OK |
Summary of the online calculation (software format) for checking by the designer and an independent checker. Final sign-off remains the responsibility of the chartered or registered engineer.
Desktop edition: calculation reports and cross-module quantity reconciliation
1. Calculation reports: with a licence, the desktop edition writes Word (.docx) and Excel (.xlsx) calculation reports and DXF drawings without the trial watermark, listing the inputs, the equations used and the results; in trial mode the step-by-step detail is hidden. For this calculator alone, licensed users can also sign in on the calculator above and formally export a single-tool Word report (with a verification code) and DXF drawing. The Pro plan (all modules) is US$990 per year; see Pricing for monthly, perpetual and team plans.
2. Cross-module reconciliation: desktop project runs carry the design peak flow into downstream channel, culvert and bridge hydraulics; terrain cut/fill into the earthwork balance, cost and carbon tables; structural concrete, formwork and rebar take-off into the cost and carbon tables; slope and excavation safety-factor thresholds into construction monitoring trigger levels.
3. Independent checking engineers, authority reviewers and academics can request a complimentary review or teaching licence (link below).
1. Worked Standard Example (Computed by the Calculation Core)
The worked example below was computed by the calculation core when this page was built; entering the same inputs above reproduces it.
Design Scenario — Standard example (calculation core defaults): The standard example uses the default inputs of the calculation core. Every number below was produced by the core when this page was built; nothing on this page is computed by hand.
The inputs below were passed to the calculation core (WebAssembly) when this page was built; every step, result and check shown here is the core's own output. Basis reported by the core: Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350)
Inputs Passed to the Calculation Core
| Parameter | Value | Unit |
|---|---|---|
| Structure Type | Open top (U-channel, open sediment basin; cantilever walls) | — |
| Clear Width | 4 | m |
| Clear Height | 2.5 | m |
| Wall Thickness | 0.3 | m |
| Base Slab Thickness | 0.35 | m |
| Base Slab Projection | 0 | m |
| External Backfill Height | (blank) | m |
| Backfill Unit Weight | 18 | kN/m³ |
| Backfill Saturated Unit Weight | 20 | kN/m³ |
| Lateral Earth Pressure Coefficient | (blank) | — |
| Surface Surcharge | 10 | kPa |
| External Groundwater Level | (blank) | m |
| Internal Water Depth | (blank) | m |
| Required Flotation Safety Factor | (blank) | — |
| Allowable Uplift Resistance of Anchors / Tension Piles | (blank) | kN/m |
| Concrete Strength f'c | 280 | kgf/cm² |
| Rebar Yield Strength fy | 4200 | kgf/cm² |
| Minimum Tension Steel Ratio | (blank) | — |
| Bar Size | Selected by program | — |
| Crack Control Method | Taiwan concrete code Art. 24.3.2 maximum bar spacing | — |
| Basin Length | (blank) | m |
Calculation Steps (calculation core output)
[HyGeoWorks online preview - not for PE sealing or submittal]
- Outer width 4.60 m (full base width 4.60 m), outer height 2.85 m; concrete 3.110 m³/m; internal water depth 2.50 m; external backfill height 2.85 m
- Load combinations: U1 = 1.4(D + F), U2 = 1.2D + 1.6H + 1.6L, U3 = 1.2(D + F) + 0.9H; service S1 = D + F, S2 = D + H + L, S3 = D + F + H
Computed Results (calculation core output)
| Output Parameter | Calculated Value | SI Unit |
|---|---|---|
| Max flexural utilization Mu / φMn | 0.982 | — |
| Max shear utilization Vu / φVc | 0.344 | — |
| Max crack control utilization (value / limit) | 0.626 | — |
| Rebar weight (estimate) | 152.9 | kg/m |
| Concrete | 3.110 | m³/m |
Verification Checks (calculation core output)
| Verification Check | Computed Value | Criterion | Verdict | Basis |
|---|---|---|---|---|
| Wall Outer face: φMn ≥ Mu and minimum steel | 63.68 kN·m/m | ≥ 62.50 | OK | Taiwan Design Code for Concrete Structures (2023) |
| Wall Outer face: crack control | 17.5 cm | ≤ 31.5 | OK | — |
| Wall Inner face: φMn ≥ Mu and minimum steel | 49.82 kN·m/m | ≥ 35.75 | OK | Taiwan Design Code for Concrete Structures (2023) |
| Wall Inner face: crack control | 22.5 cm | ≤ 40.3 | OK | — |
| Wall: φVc ≥ Vu | 158.93 kN/m | ≥ 54.71 | OK | Taiwan Design Code for Concrete Structures (2023) |
| Bottom slab Outer face: φMn ≥ Mu and minimum steel | 81.78 kN·m/m | ≥ 71.06 | OK | Taiwan Design Code for Concrete Structures (2023) |
| Bottom slab Outer face: crack control | 15.0 cm | ≤ 31.6 | OK | — |
| Bottom slab Inner face: φMn ≥ Mu and minimum steel | 60.57 kN·m/m | ≥ 57.68 | OK | Taiwan Design Code for Concrete Structures (2023) |
| Bottom slab Inner face: crack control | 20.0 cm | ≤ 31.9 | ◇ Not judged Not judged: This section is in axial tension under the governing service load combination: the service steel stress fs is calculated on the cracked section in flexure without the axial force, so fs may be underestimated (the bar spacing limit or steel stress limit checked against it is unconservative); until a tension-and-flexure section model and an independent worked example are in place, this program makes no crack control judgement; the calculated values are listed for reference. | — |
| Bottom slab: φVc ≥ Vu | 91.60 kN/m | ≥ 15.95 | OK | Taiwan Design Code for Concrete Structures (2023) |
Reinforcement and crack control (per metre of length) (4 rows)
| Member | Tension face | Mu (kN·m) | Ms (kN·m) | Required As (cm²) | Bars @ spacing (cm) | φMn (kN·m) | fs (kgf/cm²) | Crack control: value / limit | Verdict |
|---|---|---|---|---|---|---|---|---|---|
| Wall | Outer face | 62.50 | 39.06 | 7.10 | D13@17.5 | 63.68 | 2417 | 17.5/31.5 cm | PASS |
| Wall | Inner face | 35.75 | 25.54 | 5.40 | D13@22.5 | 49.82 | 2016 | 22.5/40.3 cm | PASS |
| Bottom slab | Outer face | 71.06 | 43.84 | 7.31 | D13@15.0 | 81.78 | 2112 | 15.0/31.6 cm | PASS |
| Bottom slab | Inner face | 57.68 | 41.20 | 6.30 | D13@20.0 | 60.57 | 2394 | 20.0/31.9 cm | Not judged |
Shear (2 rows)
| Member | Thickness (cm) | Vu (kN) | φVc (kN) | Vc basis | Governing combination |
|---|---|---|---|---|---|
| Wall | 30 | 54.71 | 158.93 | 0.53λ√fc'·bw·d | U2 = 1.2D + 1.6H + 1.6L (empty, external earth and water pressure) |
| Bottom slab | 35 | 15.95 | 91.60 | Table 22.5.5.1(c) with size effect λs (Art. 22.5.5.1.3) | U2 = 1.2D + 1.6H + 1.6L (empty, external earth and water pressure) |
Assumptions and Limits Stated by the Calculation Core
- Load classification (Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7): the contained liquid is fluid load F, with the same load factors and combinations as dead load; external earth pressure and pore-water pressure are H (1.6; 0.9 where permanent and counteracting the primary load)
- Lateral earth pressure coefficient K = 0.5 (0.5 when not given: the Taiwan Building Foundation Design Code (2023) Art. 7.3.1 requires an at-rest coefficient of not less than 0.5, to be raised for overconsolidated soil); backfill surface height 2.85 m, groundwater height 0.00 m (above underside of base slab)
- Analysis model: plane frame on member centrelines with uniform base reaction; section strength design includes axial tension (flexure and shear) and neglects axial compression (conservative). Not covered: two-way slab action along the tank length and partition walls, restrained thermal and shrinkage effects, seismic hydrodynamic pressure, design of construction joints and waterstops
- Sections in axial tension (Taiwan Design Code for Concrete Structures (2023) Arts. 22.2 and 22.4, tension-controlled φ = 0.90): where the moment about the tension steel Ms = Mu − Nu(d − h/2) > 0, As = As(Ms) + Nu/(φfy); where Ms ≤ 0 (whole section in tension, concrete neglected), moments are taken about the other layer, As = [Nu(h/2 − d') + Mu]/[φfy(d − d')], with d' estimated as the other face cover plus half the same bar diameter. Shear Vc includes Nu/(6Ag) (Table 22.5.5.1; tension negative, Vc not less than 0)
- Crack control: maximum bar spacing of Art. 24.3.2 (using the calculated service-load steel stress). This is a general building provision and does not address liquid tightness; where tightness matters, use the crack width or steel stress limit method
- This section is in axial tension under the governing service load combination: the service steel stress fs is calculated on the cracked section in flexure without the axial force, so fs may be underestimated (the bar spacing limit or steel stress limit checked against it is unconservative); until a tension-and-flexure section model and an independent worked example are in place, this program makes no crack control judgement; the calculated values are listed for reference
- BS EN 1992-3 Clause 7.3.1 Tightness Class 1 reference (paid standard) (source text not obtained in this verification; not verified): hydrostatic head / wall thickness hD/h = 8.3 -> interpolated crack width limit wk,max = 0.183 mm.
2. Frequently Asked Questions
Common questions about this calculator are answered below. Final sign-off remains the responsibility of the chartered or registered engineer.
Which design basis does this calculator apply?
Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7, 7.6.1.1, 22.5, 24.3.2; flotation per Taiwan Building Foundation Design Code Art. 2.12; optional direct crack width per EN 1992-1-1 7.3.4 / EN 1992-3 7.3.1 (not ACI 350). Design follows the Taiwan codes named in the basis line; the direct crack-width option uses the EN 1992 clauses named there. This is a Taiwan-code calculation offered for reference: bar sizes are D13–D32 and strengths are entered in kgf/cm².
What assumptions and limits does the calculation core state for this tool?
Load classification (Taiwan Design Code for Concrete Structures (2023) Arts. 5.3.6, 5.3.7): the contained liquid is fluid load F, with the same load factors and combinations as dead load; external earth pressure and pore-water pressure are H (1.6; 0.9 where permanent and counteracting the primary load). Lateral earth pressure coefficient K = 0.5 (0.5 when not given: the Taiwan Building Foundation Design Code (2023) Art. 7.3.1 requires an at-rest coefficient of not less than 0.5, to be raised for overconsolidated soil); backfill surface height 2.85 m, groundwater height 0.00 m (above underside of base slab). Analysis model: plane frame on member centrelines with uniform base reaction; section strength design includes axial tension (flexure and shear) and neglects axial compression (conservative). Not covered: two-way slab action along the tank length and partition walls, restrained thermal and shrinkage effects, seismic hydrodynamic pressure, design of construction joints and waterstops. Sections in axial tension (Taiwan Design Code for Concrete Structures (2023) Arts. 22.2 and 22.4, tension-controlled φ = 0.90): where the moment about the tension steel Ms = Mu − Nu(d − h/2) > 0, As = As(Ms) + Nu/(φfy); where Ms ≤ 0 (whole section in tension, concrete neglected), moments are taken about the other layer, As = [Nu(h/2 − d') + Mu]/[φfy(d − d')], with d' estimated as the other face cover plus half the same bar diameter. Shear Vc includes Nu/(6Ag) (Table 22.5.5.1; tension negative, Vc not less than 0). Crack control: maximum bar spacing of Art. 24.3.2 (using the calculated service-load steel stress). This is a general building provision and does not address liquid tightness; where tightness matters, use the crack width or steel stress limit method. This section is in axial tension under the governing service load combination: the service steel stress fs is calculated on the cracked section in flexure without the axial force, so fs may be underestimated (the bar spacing limit or steel stress limit checked against it is unconservative); until a tension-and-flexure section model and an independent worked example are in place, this program makes no crack control judgement; the calculated values are listed for reference. BS EN 1992-3 Clause 7.3.1 Tightness Class 1 reference (paid standard) (source text not obtained in this verification; not verified): hydrostatic head / wall thickness hD/h = 8.3 -> interpolated crack width limit wk,max = 0.183 mm.
Where is the calculation performed, and can the result be sealed or submitted?
The calculation runs in your browser, in the same WebAssembly calculation core this page loads. The result is an online preview: its first line reads "[HyGeoWorks online preview - not for PE sealing or submittal]".
Can I recalculate without a network connection?
Yes. "Download the offline workbench" on this page saves one HTML file that contains the workbench and the same calculation core; opened from disk it recalculates without a network connection.
3. Explore All 30 Calculators (SI Edition; Design Basis Stated on Each Page)
Each calculator below states its own design basis on its page; several apply Taiwan regulations and say so.