Check Summary Preview (Software Format; Auto-Populated)
| Check item | Trial value | Status |
|---|---|---|
| Pile Head Deflection <= 1 cm | 0.119 ≤ 1 | OK |
| Semi-Infinite Long Pile Criterion (β·L >= 3) | 5.38 ≥ 3 | OK |
Summary of the online calculation (software format) for checking by the designer and an independent checker. Final sign-off remains the responsibility of the chartered or registered engineer.
Desktop edition: calculation reports and cross-module quantity reconciliation
1. Calculation reports: with a licence, the desktop edition writes Word (.docx) and Excel (.xlsx) calculation reports and DXF drawings without the trial watermark, listing the inputs, the equations used and the results; in trial mode the step-by-step detail is hidden. For this calculator alone, licensed users can also sign in on the calculator above and formally export a single-tool Word report (with a verification code) and DXF drawing. The Pro plan (all modules) is US$990 per year; see Pricing for monthly, perpetual and team plans.
2. Cross-module reconciliation: desktop project runs carry the design peak flow into downstream channel, culvert and bridge hydraulics; terrain cut/fill into the earthwork balance, cost and carbon tables; structural concrete, formwork and rebar take-off into the cost and carbon tables; slope and excavation safety-factor thresholds into construction monitoring trigger levels.
3. Independent checking engineers, authority reviewers and academics can request a complimentary review or teaching licence (link below).
1. Governing Equations & SI Nomenclature
The equations the calculation core applies are summarised below for independent checking.
The equations below summarise the method that the calculation core applies on this page. The design basis it reports is: Chang (1937) Elastic Subgrade Reaction Beam-on-Winkler-Foundation Analytical Solution; subgrade modulus and allowable head displacement per Taiwan Building Foundation Design Code (2023) commentary and MOTC (Taiwan) Seismic Design Code for Highway Bridges Eq. C4-21. The worked example further down lists the core's own calculation steps for the standard example.
2. Worked Standard Example (Computed by the Calculation Core)
The worked example below was computed by the calculation core when this page was built; entering the same inputs above reproduces it.
Design Scenario — 1.0 m Fixed-Head Bored Pile Under H = 150 kN: Check the pile-head deflection, the head moment and the long-pile criterion β·L for a 1.0 m diameter, 20 m long fixed-head concrete pile (Ec = 33,000 MPa) in soil with an average SPT N of 15 under a horizontal load of 150 kN (normal condition).
The inputs below were passed to the calculation core (WebAssembly) when this page was built; every step, result and check shown here is the core's own output. Basis reported by the core: Chang (1937) Elastic Subgrade Reaction Beam-on-Winkler-Foundation Analytical Solution; subgrade modulus and allowable head displacement per Taiwan Building Foundation Design Code (2023) commentary and MOTC (Taiwan) Seismic Design Code for Highway Bridges Eq. C4-21
Inputs Passed to the Calculation Core
| Parameter | Value | Unit |
|---|---|---|
| Pile Diameter D | 1 | m |
| Pile Elastic Modulus Ec | 33000 | MPa |
| Effective Pile Length L | 20 | m |
| Average SPT N within 1/β below Pile Head | 15 | — |
| Loading Condition | Normal (α = 1, allowable displacement 1 cm) | — |
| Horizontal Load H | 150 | kN |
| Pile Head Fixity | Fixed Head | — |
Calculation Steps (calculation core output)
[HyGeoWorks online preview - not for PE sealing or submittal]
- EI = Ec·πD⁴/64 = 33000×10³×π×1⁴/64 = 1619884 kN·m²
- E0 = 28N kgf/cm² = 280×15 tf/m² = 41202 kPa; kH0 = α·E0/0.3 = 137340 kN/m³ (α = 1)
- kH = kH0·(BH/0.3)^(−3/4), BH = √(D/β), β = (kH·D/4EI)^¼ coupled solution -> kH = 34035 kN/m³, β = 0.2692 1/m, BH = 1.927 m
- Fixed-head pile: v0 = H/(4EIβ³) = 0.1186 cm; M0 = H/(2β) = 278.59 kN·m; max. below-grade moment = (H/2β)e^(−π/2) = 57.91 kN·m (at depth 5.83 m)
Computed Results (calculation core output)
| Output Parameter | Calculated Value | SI Unit |
|---|---|---|
| Horizontal Subgrade Modulus kH | 34035 | kN/m³ |
| Characteristic Factor β | 0.2692 | 1/m |
| Pile Head Deflection y0 | 0.1186 | cm |
| Maximum Bending Moment M_max | 278.59 | kN·m |
| Depth of First Zero Deflection l0 | 8.75 | m |
| Allowable Lateral Load H_allow | 1264.2 | kN |
Verification Checks (calculation core output)
| Verification Check | Computed Value | Criterion | Verdict | Basis |
|---|---|---|---|---|
| Pile Head Deflection <= 1 cm | 0.119 | ≤ 1 | OK | Taiwan Building Foundation Design Code, Commentary p. 5-41 |
| Semi-Infinite Long Pile Criterion (β·L >= 3) | 5.38 | ≥ 3 | OK | MOTC (Taiwan) Seismic Design Code for Highway Bridges |
3. Regional Design Options in This Edition: UK, EU, Singapore, Malaysia, Hong Kong & Australia
Symbols and units are SI unless stated otherwise.
- This calculator: the design basis is the one reported by the calculation core: Chang (1937) Elastic Subgrade Reaction Beam-on-Winkler-Foundation Analytical Solution; subgrade modulus and allowable head displacement per Taiwan Building Foundation Design Code (2023) commentary and MOTC (Taiwan) Seismic Design Code for Highway Bridges Eq. C4-21. The options listed below belong to the calculators named in each item.
- United Kingdom, Ireland & European Union: The retaining wall and slope stability calculators default to EN 1997-1:2004 Design Approach 1 (Combination 1 & Combination 2); the UK National Annex and 2nd-Gen EN 1997-1:2024 / EN 1997-3:2025 (MFA, and RFA for retaining walls) are selectable there, as are DA2 for retaining walls and DA3 for slopes. The retaining wall calculator lets γG, γQ and γφ' be overridden for a National Annex and designs metric H-bars (H10–H32) when concrete and steel strengths are entered.
- Singapore & Malaysia: The retaining wall calculator offers SS EN 1997-1:2010 with the Singapore National Annex, and the detention calculator offers a DID Malaysia MSMA 2nd Edition (2012) Equation 2.2 IDF rainfall mode besides directly entered design intensities.
- Hong Kong SAR: HyGeoWorks does not claim Hong Kong Buildings Department pre-accepted program status; the retaining wall calculator's HK GEO Geoguide 1 option shows the calculation core's steps and checks so that the result can be checked independently. With that option the calculation core applies the Geoguide 1 Table 6 and Table 7 partial factors at ULS and the §9.2.4 middle-third eccentricity check at SLS.
- Australia & New Zealand: No ARR 2019 IFD data is built in; design rainfall intensities for any AEP can be entered directly in the detention calculator. The HydroStudio desktop edition supports GDA2020 / MGA2020 zones 46–59 as well as WGS 84 / UTM zones.
4. Frequently Asked Questions
Common questions about this calculator are answered below. Final sign-off remains the responsibility of the chartered or registered engineer.
What does the criterion β·L ≥ 3 mean?
When β·L ≥ 3 the pile behaves as a semi-infinite flexible beam: the load effects die out well above the toe, so the closed-form Chang solution applies. The calculation core checks this criterion and, when β·L < 3, notes that the Chang solution is not applicable; a short rigid pile then needs another method.
How is the horizontal subgrade modulus kH obtained?
From the average SPT N within 1/β below the pile head: E0 = 28N kgf/cm², kH0 = α·E0/0.3 with α = 1 (normal) or 2 (seismic), and kH = kH0·(BH/0.3)^(−3/4) with BH = √(D/β), solved together with β per MOTC (Taiwan) Seismic Design Code for Highway Bridges Eq. C4-21, as reported by the calculation core.
Which pile-head deflection limit is checked?
1 cm for the normal condition and 1.5 cm for the seismic condition, per the Taiwan Building Foundation Design Code commentary (p. 5-41), as reported by the calculation core. If your design code or the supported structure needs a different limit, compare the reported deflection with that value.
What changes with a free pile head?
A free head rotates, so the head deflection doubles compared with a fixed head and the maximum moment occurs below ground rather than at the head. For a free head an applied head moment Mt can also be entered.
5. Explore All 30 Calculators (SI Edition; Design Basis Stated on Each Page)
Each calculator below states its own design basis on its page; several apply Taiwan regulations and say so.