Eurocode Reference Notes: EC2 Shear Size Factor k, EC7 Design Approach 1 Partial Factors and Embedded Wall Overdig

These notes collect code expressions and factors together with their sources. The partial factors are the EN 1997-1:2004 Annex A recommended values held in the platform's code library; National Annexes may change them.

Summary table

→ Open the retaining wall calculator (Eurocode 7 Design Approach 1, Combinations 1 and 2 by default)

TopicExpression or valuesSource
EC2 shear resistance without shear reinforcementVRd,c = [CRd,c k (100 ρl fck)^(1/3)] bw d, with k = 1 + sqrt(200/d), limited to 2.0 (d in mm), and CRd,c = 0.18/γcEN 1992-1-1 clause 6.2.2(1), as quoted in JRC report EUR 26566 EN (2014), p. 92
EC7 Design Approach 1 combinationsCombination 1: A1 + M1 + R1. Combination 2: A2 + M2 + R1EN 1997-1:2004 Annex A recommended values, as tabulated in JRC report EUR 26227 EN (2013)
Action factors, sets A1 and A2Permanent unfavourable 1.35 and 1.0; permanent favourable 1.0 and 1.0; variable unfavourable 1.5 and 1.3EN Table A.3 (JRC EUR 26227 EN, Table 3.3.1)
Soil parameter factors, sets M1 and M2On tan φ': 1.0 and 1.25; on c': 1.0 and 1.25; on cu: 1.0 and 1.4; on weight density: 1.0 and 1.0EN Table A.4 (JRC EUR 26227 EN, Table 4.3.2)
Retaining structure resistance factors, set R1Bearing 1.0; sliding 1.0; earth resistance 1.0EN Table A.13 (JRC EUR 26227 EN, Tables 4.3.2 and 4.3.3)
Unplanned excavation allowance for embedded walls (ULS)10% of the retained height for cantilever walls, or 10% of the height below the lowest support for supported walls, up to a maximum of 0.5 mJRC report EUR 26227 EN (2013), Table 7.2.4

Notes and Conditions of Use

  • National Annexes may change the factor values and the design approaches permitted in a country; check the Annex that applies to the project.
  • The retaining wall and slope stability calculators use Design Approach 1 (Combinations 1 and 2) by default; other options listed on those pages are selectable.
  • The counterfort wall, pile cap, box culvert and liquid-retaining calculators follow Taiwan codes and do not apply the EC2 shear expression above.

Frequently Asked Questions

Which combination governs a retaining wall under Design Approach 1?

It depends on the wall, the ground and the loading, so both combinations have to be verified. Combination 1 applies the A1 action factors (1.35 on unfavourable permanent actions and 1.5 on unfavourable variable actions); Combination 2 applies the M2 material factors (1.25 on tan φ' and c') with the A2 action factors.

Are these the UK National Annex values?

The table gives the Annex A recommended values of EN 1997-1:2004 as held in the library. A National Annex can set different values, so check the one that applies. The retaining wall calculator offers BS EN 1997-1:2004 with the UK National Annex as a selectable option.