Eurocode Reference Notes: EC2 Shear Size Factor k, EC7 Design Approach 1 Partial Factors and Embedded Wall Overdig
These notes collect code expressions and factors together with their sources. The partial factors are the EN 1997-1:2004 Annex A recommended values held in the platform's code library; National Annexes may change them.
Summary table
→ Open the retaining wall calculator (Eurocode 7 Design Approach 1, Combinations 1 and 2 by default)
| Topic | Expression or values | Source |
|---|---|---|
| EC2 shear resistance without shear reinforcement | VRd,c = [CRd,c k (100 ρl fck)^(1/3)] bw d, with k = 1 + sqrt(200/d), limited to 2.0 (d in mm), and CRd,c = 0.18/γc | EN 1992-1-1 clause 6.2.2(1), as quoted in JRC report EUR 26566 EN (2014), p. 92 |
| EC7 Design Approach 1 combinations | Combination 1: A1 + M1 + R1. Combination 2: A2 + M2 + R1 | EN 1997-1:2004 Annex A recommended values, as tabulated in JRC report EUR 26227 EN (2013) |
| Action factors, sets A1 and A2 | Permanent unfavourable 1.35 and 1.0; permanent favourable 1.0 and 1.0; variable unfavourable 1.5 and 1.3 | EN Table A.3 (JRC EUR 26227 EN, Table 3.3.1) |
| Soil parameter factors, sets M1 and M2 | On tan φ': 1.0 and 1.25; on c': 1.0 and 1.25; on cu: 1.0 and 1.4; on weight density: 1.0 and 1.0 | EN Table A.4 (JRC EUR 26227 EN, Table 4.3.2) |
| Retaining structure resistance factors, set R1 | Bearing 1.0; sliding 1.0; earth resistance 1.0 | EN Table A.13 (JRC EUR 26227 EN, Tables 4.3.2 and 4.3.3) |
| Unplanned excavation allowance for embedded walls (ULS) | 10% of the retained height for cantilever walls, or 10% of the height below the lowest support for supported walls, up to a maximum of 0.5 m | JRC report EUR 26227 EN (2013), Table 7.2.4 |
Notes and Conditions of Use
- National Annexes may change the factor values and the design approaches permitted in a country; check the Annex that applies to the project.
- The retaining wall and slope stability calculators use Design Approach 1 (Combinations 1 and 2) by default; other options listed on those pages are selectable.
- The counterfort wall, pile cap, box culvert and liquid-retaining calculators follow Taiwan codes and do not apply the EC2 shear expression above.
Frequently Asked Questions
Which combination governs a retaining wall under Design Approach 1?
It depends on the wall, the ground and the loading, so both combinations have to be verified. Combination 1 applies the A1 action factors (1.35 on unfavourable permanent actions and 1.5 on unfavourable variable actions); Combination 2 applies the M2 material factors (1.25 on tan φ' and c') with the A2 action factors.
Are these the UK National Annex values?
The table gives the Annex A recommended values of EN 1997-1:2004 as held in the library. A National Annex can set different values, so check the one that applies. The retaining wall calculator offers BS EN 1997-1:2004 with the UK National Annex as a selectable option.
Sources and disclaimer: values on these pages come from the platform's code-constants library, from producers' published section tables, or from the official publications named in each row. Rows that cite the UK Government GHG Conversion Factors contain public sector information licensed under the Open Government Licence v3.0. Standards (EN, BS) are cited by number only and their text is not reproduced. These pages are a design aid, not an official document; check the current source before use. Calculations must be checked and approved by a suitably qualified engineer.